ZW32-12MF outdoor high voltage permanent Magnet Vacuum Circuit Breaker
ZW32-12MF outdoor high voltage permanent Magnet Vacuum Circuit Breaker
ZW32-12MF outdoor high voltage permanent Magnet Vacuum Circuit Breaker
+
  • ZW32-12MF outdoor high voltage permanent Magnet Vacuum Circuit Breaker
  • ZW32-12MF outdoor high voltage permanent Magnet Vacuum Circuit Breaker
  • ZW32-12MF outdoor high voltage permanent Magnet Vacuum Circuit Breaker

ZW32-12MF Permanent Magnet Vacuum Circuit Breaker

When a fault occurs in the T-connected branch line of a 12kV overhead distribution line or in the end user, the protection action time limit of the incoming switch cannot be reasonably adjusted with the protection time limit of the substation outgoing switch, which will cause the substation outgoing switch to trip. If the fault is permanent and the substation reclosing will fail, a local fault in the medium-voltage user boundary will cause the entire 12kV distribution line to be shut down.

If an outdoor boundary circuit breaker is installed at the T-connection or user end (responsibility boundary point), after confirming that a fault (overcurrent, short circuit, single-phase grounding, etc.) has occurred in the user boundary, the fault is automatically isolated, which can ensure normal power supply to users in non-fault areas.

The application of ZW32-12M outdoor high-voltage permanent magnetic vacuum circuit breaker on 12kV feeder overhead lines can avoid the joint fault power outage of fault-free lines, reduce the scope of fault power outage, shorten the power outage time of users, and protect the safe operation of the main network. It also has fault detection, protection control and communication functions, and can automatically cut off single-phase grounding faults and automatically isolate interphase short-circuit faults. The installation point is used at the responsibility demarcation point of the 12kV distribution line user incoming line, and can also be used at the branch line connection that meets the requirements.

Outline and installation size (mm):

Working Conditions:

  • Ambient temperature: not higher than +40℃, not lower than -40℃;
  • Relative humidity: daily average value not greater than 95%, monthly average value not greater than 90%;
  • Altitude not exceeding 2000 meters;
  • Wind pressure not exceeding 700Pa (equivalent to wind speed 34m/s);
  • Earthquake intensity not exceeding 8 levels;
  • No fire, explosion, serious pollution, chemical corrosion or severe vibration.

Main Technical Parameters of Circuit Breaker:

Project Parameter
Rated voltage 12kv
Rated current 630A, 1250A
Rated frequency 50Hz
Power frequency withstand voltage (1min) Dry type (phase to phase, to ground/break) 42kv / 48kv
Wet test (to ground, external insulation) 34kv
Lightning impulse withstand current (peak value) (phase to phase, to ground/break) 75kA / 85kA
Rated short-circuit breaking current 20kA 25kA
Rated short-circuit making current (peak value) 50kA 63kA

Main Mechanical parameters of Circuit Breaker:

Project Parameter
Rated peak withstand current 50kA 63kA
4S short-time withstand current 20kA 25kA
Rated operating cycle Open -0.3s- Close Open -180s- Close Open
Rated short-circuit current breaking times 30 Times
Mechanical life 30000 Times
Secondary circuit 1min power frequency withstand voltage 2kv
Contact opening distance 9±1 mm
Contact overtravel 2.5 ±1 mm
Opening speed 1.1 ±0.3 m/s
Closing speed 0.6 ±0.2 m/s
Contact closing bounce time ≤ 2 ms
Phase center distance 340 ±2 mm
Three-phase opening and closing out of phase ≤ 2 ms
Conductive circuit resistance of each phase ≤ 80(with isolation ≤ 150)
Weight about 70kg

ZW32-12MF outdoor high voltage permanent Magnet Vacuum Circuit Breaker


When a fault occurs in the T-connected branch line of a 12kV overhead distribution line or in the end user, the protection action time limit of the incoming switch cannot be reasonably adjusted with the protection time limit of the substation outgoing switch

隐藏域元素占位

  • 产品描述
    • Commodity name: ZW32-12MF outdoor high voltage permanent Magnet Vacuum Circuit Breaker

    When a fault occurs in the T-connected branch line of a 12kV overhead distribution line or in the end user, the protection action time limit of the incoming switch cannot be reasonably adjusted with the protection time limit of the substation outgoing switch

    ZW32-12MF Permanent Magnet Vacuum Circuit Breaker

    When a fault occurs in the T-connected branch line of a 12kV overhead distribution line or in the end user, the protection action time limit of the incoming switch cannot be reasonably adjusted with the protection time limit of the substation outgoing switch, which will cause the substation outgoing switch to trip. If the fault is permanent and the substation reclosing will fail, a local fault in the medium-voltage user boundary will cause the entire 12kV distribution line to be shut down.

    If an outdoor boundary circuit breaker is installed at the T-connection or user end (responsibility boundary point), after confirming that a fault (overcurrent, short circuit, single-phase grounding, etc.) has occurred in the user boundary, the fault is automatically isolated, which can ensure normal power supply to users in non-fault areas.

    The application of ZW32-12M outdoor high-voltage permanent magnetic vacuum circuit breaker on 12kV feeder overhead lines can avoid the joint fault power outage of fault-free lines, reduce the scope of fault power outage, shorten the power outage time of users, and protect the safe operation of the main network. It also has fault detection, protection control and communication functions, and can automatically cut off single-phase grounding faults and automatically isolate interphase short-circuit faults. The installation point is used at the responsibility demarcation point of the 12kV distribution line user incoming line, and can also be used at the branch line connection that meets the requirements.

    Outline and installation size (mm):

    Working Conditions:

    • Ambient temperature: not higher than +40℃, not lower than -40℃;
    • Relative humidity: daily average value not greater than 95%, monthly average value not greater than 90%;
    • Altitude not exceeding 2000 meters;
    • Wind pressure not exceeding 700Pa (equivalent to wind speed 34m/s);
    • Earthquake intensity not exceeding 8 levels;
    • No fire, explosion, serious pollution, chemical corrosion or severe vibration.

    Main Technical Parameters of Circuit Breaker:

    Project Parameter
    Rated voltage 12kv
    Rated current 630A, 1250A
    Rated frequency 50Hz
    Power frequency withstand voltage (1min) Dry type (phase to phase, to ground/break) 42kv / 48kv
    Wet test (to ground, external insulation) 34kv
    Lightning impulse withstand current (peak value) (phase to phase, to ground/break) 75kA / 85kA
    Rated short-circuit breaking current 20kA 25kA
    Rated short-circuit making current (peak value) 50kA 63kA

    Main Mechanical parameters of Circuit Breaker:

    Project Parameter
    Rated peak withstand current 50kA 63kA
    4S short-time withstand current 20kA 25kA
    Rated operating cycle Open -0.3s- Close Open -180s- Close Open
    Rated short-circuit current breaking times 30 Times
    Mechanical life 30000 Times
    Secondary circuit 1min power frequency withstand voltage 2kv
    Contact opening distance 9±1 mm
    Contact overtravel 2.5 ±1 mm
    Opening speed 1.1 ±0.3 m/s
    Closing speed 0.6 ±0.2 m/s
    Contact closing bounce time ≤ 2 ms
    Phase center distance 340 ±2 mm
    Three-phase opening and closing out of phase ≤ 2 ms
    Conductive circuit resistance of each phase ≤ 80(with isolation ≤ 150)
    Weight about 70kg

Get A Quote