Overview:
DSY-DWDF10-12/24 adopts prefabricated, touchable, live silicone rubber cable heads, which are fully sealed, fully insulated, and maintenance-free, ensuring reliable personal safety. The structure is compact, with a small and aesthetically pleasing appearance. The double-layer stainless steel cabinet has a service life of more than 20 years. Under the premise of not affecting the operation of the main network, it allows for regional power outages for maintenance, reducing the range of power outages. It can be equipped with one or more ring main units. The wiring options are flexible and diverse, with up to eight branch circuits. Optional components include lightning arresters, short-circuit fault indicators, current-limiting fuses, etc., This switchgear to meet various user requirements.
Features:
- Adopts prefabricated, touchable, live silicone rubber cable heads, fully sealed, fully insulated, maintenance-free, ensuring reliable personal safety;
- Compact structure with a small and aesthetically pleasing appearance, featuring a double-layer stainless steel cabinet with a service life of over 20 years;
- Allows for regional power outages for maintenance without affecting the operation of the main network, reducing the outage range;
- Can be equipped with one or more SF6 load switches. The wiring options are flexible and diverse, with up to 8 branch circuits;
- Optional components include lightning arresters, short-circuit fault indicators, and current-limiting fuses, to meet various user requirements.
Electrical technical parameters:
|
Project |
Parameter |
Parameter |
|
Rated current |
12kV |
24kV |
|
Rated volatge |
630A |
630A |
|
Power frequency withstand voltage (phase to ground) |
42kV/min |
79kV/min |
|
Lightning impulse voltage |
75kV |
95kV |
|
Rated breaking current |
630A |
630A |
|
Rated short-circuit breaking current (peak value) |
50kA |
50kA |
|
Rated short-time withstand current |
25kA/4S |
25kA/4S |
|
Rated peak withstand current |
50kA |
50kA |
|
Rated breaking capacitance current |
45A |
45A |
|
Rated breaking inductance current |
16A |
16A |
|
Full load breaking times |
>100 |
>100 |
|
Number of mechanical operations of opening and closing |
2000 |
2000 |